电缆的型号 Type and
Decription 型号 Type
| 名称
Description
| 适用范围
Application
| | | YJV YJLV |
铜芯(铝芯)交联聚乙烯绝缘聚氯乙烯护套电力电缆 Copper(aluminum)conductor,XLPE insulated and
PVC sheathed cable | 敷设在室内,隧道及管道中,不能承受机械外力 For laying indoors,in tunnel or pipe,unable to bear external mechanical
force | |
| YJY YJLY
| 铜芯(铝芯)交联聚乙烯绝缘聚乙烯护套电力电缆
Copper(aluminum)conductor,XLPE insulated and PE sheathed cable | | | YJV22 YJLV22 | 铜芯(铝芯)交联聚乙烯绝缘钢带铠装聚氯乙烯护套电力电缆 Copper(aluminum)conductor,XLPE insulated,steel tape armored and PVC sheathed
cable | 室内,隧道,电缆沟内,或埋地敷设等,能承受一定的机械外力,但不能承受大的拉力 For laying indoors,in tunnel,cable trench,or direct in ground,can bear external mechanical force ,while unable to bear large tension |
| | YJV23 YJLV23 | 铜芯(铝芯)交联聚乙烯绝缘钢带铠装聚乙烯护套电力电缆 Copper(aluminum)conductor,XLPE insulated,steel tape armored
and PE sheathed cable | | | YJV32
YJV42 YJLV42 YJLV32 | 铜芯(铝芯)交联聚乙烯绝缘细(粗)钢丝铠装聚氯乙烯护套电力电缆
Copper(aluminum)conductor,XLPEinsulated,thin(thick) steel wire armored and PVC sheathed cable | 敷设在高落差地区,能承受一定的机械外力和一定的拉力
For laying in high drop area ,can bear external mechanical force and certain tension | |
|
YJV33 YJV43 YJLV43 YJLV33 | 铜芯(铝芯)交联聚乙烯绝缘细(粗)钢丝铠装聚乙烯护套电力电缆 Copper(aluminum)conductor,XLPE
insulated,thin(thick) steel wire armored and PE sheathed cable | | |
| 备注:公司还可生产62、72规格的产品。 Notes: We can also produce non-magnetic steel tape
and metal wire armored cable | |
产品标准 Standard of Product 本产品按GB/T12706-2002《额定电压1KV(Um=1.2KV)
到35Kv(Um=40.6KV)挤包绝缘电力电缆及附件》标准生产,同时还可根据用户需要按国际电工委员会推荐标准IEC、英国标准、德国标准及美国标准生产。 The product is manufactured according to
the standard of GB/T12706-2002.At the same time ,it can also be manufactured according to IEC, BS, DIN and AEIC upon request.
适用范围 Application 本产品适用于工频额定电压3.6/6kV~26/35kV输配电线路作配送电能之用。 The product is suitable for power transmission and distribution lines with rated power frequency voltage
3.6/6kV~26/35kV.
使用特性 Operating
Characteristic 工频额定电压Uo/U为3.6/6kV~26/35kV。 Power frequency rated voltage Uo/U:
3.6/6kV~26/35kV 电缆导体允许的长期**工作温度:90℃。 Max. permissible continuous operating temperature of the conductor: 90℃. 短路时(最长时间不超过5s)电缆导体的**温度不超过250℃。 Max. temperature of conductor during short-circuit (5s
maximum duration) shall not exceed 250℃. 电缆敷设时环境温度应不低于0℃。 The ambient temperature under installation should not below 0℃. 电缆弯曲半径:单芯电缆不小于电缆外径20倍;多芯电缆不小于电缆外径15倍。 The bending radius of a single-core cable: not less than 20 times of cable’s OD The bending radius of a
multi-core cable: not less than 15 times of cable’s.OD
电缆敷设运行条件 The installation operating condition
of cable 电缆导体的允许长期**工作温度: 90℃。 Max. permissable continuous operating temperature of the conductor: 90℃. 环境空气温度:40℃。 Ambient air temperature: 40℃. 土壤温度:25℃。 Soil temperature: 25℃. 土壤热阻系数:1.0k.m/w。 Thermal resistivity of soil: 1.0k.m/w. 埋设深度:0.7m Depth of laying:
0.7m. 仅考虑一个回路 Only consider a loop 单芯电缆为水平敷设,间距为一个电缆外径。 If the single-core cable is paralleled
laid, adjacent space is equivalent to cable’s OD.. 不同土壤温度下的载流量修正系数 Correction factor of current rating under different soil temperature 导体工作温度 Operating Temperature of Conductor | 环境温度℃(土壤中) Ambient Temperature in Soil
| 10 |
15 | 20 | 25
| 30 | 35 | 载流量修正系数 Correction Factor of Current Rating | 90℃ | 1.11 | 1.07
| 1.04 | 1.00 | 0.96
| 0.92 |
不同土壤热阻系数的载流量修正系数 Correction factor of current rating under
different soil thermal resistivity 导体工作温度 Operating Temperature of
Conductor | 电压等级(KV) Rated Voltage | 土壤热阻系数(k.m/w)Soil Thermal Resistivity
| 0.8 |
1.0 | 1.2
| 1.5 | 载流量修正系数 Correction Factor of Current Rating | 90℃ | 0.6/1-6/6 | 1.08 | 1.0
| 0.95 | 0.77 | 6/10-12/15 | 1.06
| 1.0 | 0.94 | 0.78
| 12/20-26/35 |
1.06 | 1.0 | 0.94
| 0.80 |
不同环境温度下的载流量修正系数 Correction factor of current rating under
different air temperature 导体工作温度 Operating Temperature of
Conductor | 环境温度℃(空气中) Ambient Temperature in Air | 20 | 25 | 30
| 35 | 40 | 45
| 50 | 55 | 载流量修正系数 Correction Factor of Current Rating | 90℃ | 1.23 | 1.17
| 1.12 | 1.06 | 1.00